To set up the driver
Carrier® ChillerVu™
(OPN-PSM-MPCXPE) Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Start-up Guide 45 All rights reserved
If you have a new Carrier® ChillerVu™, you may have to ascertain if it has a driver that allows i-Vu® or Field
Assistant to find it. If the controller is not already equipped with the v6.02.028 or later driver, or you are not sure
which driver is in the Carrier® ChillerVu™, you must ascertain the present driver and download the correct one.
You can use AppLoader or PuTTY to determine the driver in the controller in a Modstat.
You may want to change the driver's properties in the i-Vu® interface to suit your application.
1 In the i-Vu® navigation
tree, right-click the Carrier® ChillerVu™ and click
from the drop-
down menu.
2 Make changes as needed on the
page for
.
On the
page, you can change the following properties:
• Backup battery conservation settings. See table below.
• Module clock synchronization and failure. See table below.
• Network Input microblock communication properties.
Turn off internal backup
battery after ___ days to
conserve battery life (shutoff
date/time)
How long backup battery should run after power loss.
Downloading activates the battery backup. To conserve battery life when
you know the Carrier® ChillerVu™ will be without power for an extended period
after downloading (for example, during shipment):
1 Verify the
LED is lit, then set this field to 0.
2 After you install the Carrier® ChillerVu™ and apply power, enter a number
greater than 0.
TouchScreen Schedule Edit
Enable
Check this field to allow a user to edit this controller's schedules from an
Equipment Touch's Schedules screen.
Date and time the control program uses when controller's real-time clock is
invalid.
Use an occupied date and time (such as a Tuesday at 10 a.m.) so the
equipment does not operate in unoccupied mode if the controller loses power
during occupancy.