Wiring devices to the Carrier® ChillerVu™'s Rnet port
Carrier® ChillerVu™
(OPN-PSM-MPCXPE) Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Start-up Guide 32 All rights reserved
The standard control programs that are included with the Carrier® ChillerVu™ library do not use communicating
sensors or the Equipment Touch.
A custom control program could allow you to use and connect the following to the Rnet port:
Up to 15 ZS sensors (5 per control program)
One Wireless Adapter that communicates with up to 15 wireless sensors
One Equipment Touch
Up to 4 SPT Standard sensors and one SPT Plus, SPT Pro, or SPT Pro-F sensor
NOTE
ZS sensors, a Wireless Adapter, and an Equipment Touch can share the Rnet, but not SPT sensors.
To configure the control program for the desired user interaction with the ZS or wireless sensors, see the ZS
Sensor Application Guide or the Wireless Sensor Application Guide.
For detailed installation instructions, see the Carrier Sensors Installation Guide for SPT sensor information, ZS
Sensor Installation Guide, Wireless Sensor Installation Guide, or the Equipment Touch Installation and Setup
Guide.