Wiring for communications
Carrier® ChillerVu™
(OPN-PSM-MPCXPE) Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Start-up Guide 26 All rights reserved
1 Turn
the Carrier® ChillerVu™'s power.
2 Verify that DIP switch
is set to
.
3 Verify that Port S2 is set up for EIA-485 2-wire (Half Duplex). .
4 Connect the Carrier® ChillerVu™'s Port S2 to the CCN bus. Use the same polarity throughout the network
segment.
Wire this Port S2 terminal
To this CCN device terminal
Signal Ground (Pin 5)
Net- (Pin 2)
Net+ (Pin 1)
The CCN Shield should be tied/taped back or daisy chained if the Carrier® ChillerVu™ is not at one
end of the bus.
5 Turn
the Carrier® ChillerVu™'s power.
The default CCN address for the Carrier® ChillerVu™ is Bus 0, Element 1. See To scan and download CCN
devices (page
34).