MPC Open XPIO48 and MPC Open XPIO816 specifications
Power
24 Vac ±10%, 50–60 Hz
40 VA power consumption
26 Vdc (25 V min, 30 V max), 21 W
Single Class 2 source only, 100 VA or less
24 Vac ±10%, 50–60 Hz
45 VA power consumption
26 Vdc (25 V min, 30 V max), 21 W
Single Class 2 source only, 100 VA or less
Inputs
8 inputs, configurable for 0–5 Vdc, 0–10 Vdc, 0–20 mA, RTD, thermistor, or dry
contact
16 inputs, configurable for 0–5 Vdc, 0–10 Vdc, 0–20 mA, RTD, thermistor, or dry
contact
Input resolution 14 bit A/D
Input pulse frequency 40 pulses per second. Minimum pulse width (on or off time) required for each
pulse is 12.5 msec.
Outputs
4 outputs for 24 Vdc relay driver, 0–10 Vdc, or 0-20 mA
8 outputs for 24 Vdc relay driver, 0–10 Vdc, or 0-20 mA
Output resolution 12 bit D/A
Microprocessor 8-bit microprocessor with 60 kB Flash memory, 2 kB SRAM, and CAN controller
Protection
Incoming power - 2 replaceable 3 Amp Pico
®
fuses
Power, network, I/O connections - protected against voltage transient and surge
events
Status indicators LED's indicate status of communications, running, errors, and outputs
Environmental operating
range
-20 to 140°F (-29 to 60°C), 10–90% relative humidity, non-condensing
Install in a UL Listed enclosure only.
Storage temperature range -24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
Physical Rugged aluminum cover, removable screw-type terminal blocks