Installing an MPC Open XPIO expander
Carrier® ChillerVu™
(OPN-PSM-MPCXPE) Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Start-up Guide 14 All rights reserved
To wire the expander for power
CAUTIONS
• The expanders are powered by a Class 2 power source. Take appropriate isolation measures when mounting
it in a control panel where non-Class 2 circuits are present.
• For the Carrier® ChillerVu™ to recognize an attached expander, you must turn on the expander before you
turn on the controller.
1 Verify that the expander's power switch is in the
position.
2 Connect the 24 Vac power source to the
and
terminals, being sure to maintain proper
polarity if power is being shared.
3 Turn on the expander's power switch.
4 Verify that the expander's
LED is on and the
LED is blinking.
Do not exceed 100 feet total wire length.
1 Wire the controller's
port to the same port on the expander.
Connect:
○ Gnd to Gnd
○ Xnet- to Xnet-
○ Xnet+ to Xnet+
To use more than one expander, wire their
ports together in a daisy-chain
configuration. The Carrier® ChillerVu™ must be the first device on the expander network.
2 You must set the Xnet baud rate to 500 kbps in the i-Vu® interface on the driver's
page. See To set up
the driver.
3 If the expander network has more than one expander, place the
jumper in the down position or remove
it from all expanders except the one at the end of the expander network. The
jumper must be in the up
position on the expander at the end of the network.