Addressing the Carrier® ChillerVu™
Carrier® ChillerVu™
(OPN-PSM-MPCXPE) Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Start-up Guide 10 All rights reserved
•
— If there is a DHCP server on the network, and if you have a single Carrier® ChillerVu™ or multiple
Carrier® ChillerVu™s that exist on the SAME subnet, use DHCP addressing. Skip to the section To obtain an
IP address using DHCP (page 11).
•
— If you have multiple Carrier® ChillerVu™s that reside on different subnets, you
cannot use DHCP addressing. Instead, give each Carrier® ChillerVu™ an assigned IP address. Skip to the
section To assign a custom IP address (page 11).
This network configuration also requires that you configure IP Broadcast Management Devices
(BBMDs). See To set up BACnet Broadcast Management Devices. (page
41)
To use a default IP address
The IP address must be unique on the Ethernet.
1 If wired for power, turn off the controller's power.
2
The controller only reads the rotary switch positions during power up or upon reset.
3 Set the
DIP switch to
(
).
4 Use the rotary switches to set the Carrier® ChillerVu™'s address. Set the
(
) switch to the tens digit
of the address, and set the
(
) switch to the ones digit.
If the controller’s address is 25, point the arrow on the
(
) switch to 2 and the arrow on
the
(
) switch to 5.
10's 1's
1
3
4
5
2
7
8
9
6
0
1
3
4
5
2
7
8
9
6
0
5 Set the
DIP switch to
to add 100 to
in the IP address.
If you turn on this DIP switch and the controller network MAC address is 25, the IP address is
192.168.168.125.
6 Connect Port E1, which is the only port that speaks BACnet over IP.
The default address is an intranet address. Data packets from this address are not routable to the Internet.