Configuring CCN PIC files to communicate with Chiller Manager
Carrier® ChillerVu™
(OPN-PSM-MPCXPE) Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Start-up Guide 39 All rights reserved
Before proceeding, you must have already:
• Created your i-Vu® database
• Discovered and downloaded the CCN PIC's to the Carrier® ChillerVu™ controller
• Created and added the Chiller Manager control programs to the i-Vu® database
To enable the CCN PIC equipment files to communicate with the Chiller Manager program, you must edit the
for the chillers.
Right-click on the Carrier® ChillerVu™ in the navigation tree and select
.
1 Change the
to #chiller_x, where x is the chiller number.
For a 3-chiller system, the chiller reference names are:
○ #chiller_1
○ #chiller_2
○ #chiller_3
2 Click
.
3 Repeat steps 1 and 2 to rename every chiller.
4 To verify your chiller connections in the i-Vu® interface, select the Chiller Manager program in the navigation
tree and go to the
>
tab. If you see any errors on the pre-configured network
points, review your
edits.
Configuring CCN PIC files to communicate with Chiller Manager