Adding the Carrier® ChillerVu™ into the i-Vu® or Field Assistant system
Carrier® ChillerVu™
(OPN-PSM-MPCXPE) Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Start-up Guide 38 All rights reserved
4 Under
, expand
>
.
5 Select
Port S2 is connected to the LonWorks network
.
6 Select
.
7 Set
to 38.4 kbps.
This is the the baud rate between the LonWorks Option Card and the Carrier® ChillerVu™, not the
LonWorks network.
8 Select
for
.
9 Accept all other default settings.
10 Click
.
LonWorks network using the SLTA-10
1 Verify the
DIP switch (5)
is
and the controller's power has been cycled.
2 In the i-Vu® navigation tree, right-click the Carrier® ChillerVu™ and select
from the drop-
down menu.
3 Under
, expand
>
.
4 Under
, select
for
is connected to the LonWorks network
, then select
.
5 Set
to 57.6 kpbs.
This is the the baud rate between the LonWorks SLTA-10 and the Carrier® ChillerVu™, not the
LonWorks network.
6 Accept all other default settings.
7 Click
.