Troubleshooting
Carrier® ChillerVu™
(OPN-PSM-MPCXPE) Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Start-up Guide 60 All rights reserved
Before replacing the fuse, try to determine why the fuse blew.
Check the Power wiring polarity of the Carrier® ChillerVu™, any attached expanders, and any other controllers
that share the power supply. Use the same polarity for all of them.
Verify that outputs are wired to the appropriate types of devices. See Outputs (page 18). For example, you
cannot wire a 24 Vac device to an output.
Carrier® ChillerVu
- If the
Aux Power Out
port is used, verify that it is wired correctly. See To wire inputs
and outputs (page
18).
To replace the fuse:
1 Turn
off
the Carrier® ChillerVu™'s power.
2 If the fuse is on an expander, remove the coverplate.
3 Using needle-nose pliers, pull the bad fuse from the Carrier® ChillerVu™.
4 Cut the wires on the new fuse so that the total length is approximately 1 inch and the fuse is centered.
1 inch
5 Bend the wire ends so that the length is approximately 1/2 inch.
inch
2
1
/
6 Use the pliers to grip one wire end of the fuse and push into a fuse socket on the Carrier® ChillerVu™.
7 Grip the other wire end of the fuse and push into the other fuse socket.
8 If working on an expander, replace the coverplate.
9 Turn on the power and verify that the Power LED is lit.
To take the Carrier® ChillerVu™ out of service
If needed for troubleshooting or start-up, you can prevent the i-Vu® application from communicating with the
Carrier® ChillerVu™ by shutting down communication from the controller to the i-Vu® application. When
Out of
Service
, i-Vu® no longer communicates properties, colors, trends, etc..
1 On the i-Vu® navigation
tree, select the Carrier® ChillerVu™.
2 On the
Properties
page, check
Out of Service
.
3 Click
Accept
.