To set up the driver
Carrier® ChillerVu™
(OPN-PSM-MPCXPE) Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Start-up Guide 48 All rights reserved
Calendars are provided in the driver for BACnet compatibility only. Instead, use the
feature in the i-Vu®
interface.
Common and Specific Alarms
On these pages, you can enable/disable, change BACnet alarm properties, or set delays for the following BACnet
alarms:
• All Programs Stopped
• Duplicate Address
• Locked I/O
• Control Program
• Program Stopped
•
• Low Battery Alarm
To set up alarm actions for controller generated alarms, see "Setting up alarm actions" in i-Vu® Help.
Short message shown on the
page or in an alarm action when this type of
alarm is generated.
Alarm Category and Alarm
Template
See "Alarms" in i-Vu® Help.
Clear these checkboxes to disable Alarm or Return to normal messages of this
type from this controller.
Do not change this field.
Custom Translation Tables
You can set up a translation table that an analog input will use to translate the raw data from a non-linear sensor
to the engineering units you want it to output on the wire. In the navigation tree, select
Custom Translation Table
#1
,
, or
. The
page has instructions. For the input to use the translation table, navigate to the
input, select the
tab, then set
Sensor Type (Scaling Method)
to
Non-Linear, Custom Table #__
.