Troubleshooting
Carrier® ChillerVu™
(OPN-PSM-MPCXPE) Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Start-up Guide 58 All rights reserved
The
and
LED's indicate expander and network status.
2 flashes per second Off Normal
5 flashes per second 2 flashes per second Boot is running or driver is updating
5 flashes per second On Fatal error. Replace expander or return for repair.
To restore factory defaults
This erases all archived information and user-configuration settings. You will have to reconfigure
all custom settings. It is recommended to restore the factory defaults only under the guidance of Carrier Control
Systems Support.
To erase volatile memory data and restore factory default configuration settings:
1 Turn off the Carrier® ChillerVu™'s power switch.
2 Make sure the address switches are not set to 0, 0.
3 Hold down the controller’s
button while you turn its power on.
4 Continue to hold down the
button until the controller displays
and then the chase pattern,
then release the button.
5 Turn on the Carrier® ChillerVu™'s power switch.
If you have a CCN network and you restore factory defaults, you must download to the Carrier®
ChillerVu™ from the i-Vu® application and NOT upload it. Uploading results in losing your CCN communication.
If you need the Carrier® ChillerVu™'s serial number when troubleshooting, the number is on:
• a sticker on the back of the main controller board
• a Module Status report (Modstat) under
(or
)
To obtain a modstat in the i-Vu® interface:
1 Select the Carrier® ChillerVu™ in the navigation tree.
2 Right-click and select
.