62-61753-21   
YES - Indicates to the microprocessor that the set 
point is to be displayed in tenths of a degree. 
NO - Indicates to the microprocessor that the set 
point is to be displayed in whole numbers. 
Not supported for Vector MULTI-TEMP at this time 
USE FACTORY DEFAULT SETTING ONLY, DO 
NOT OPERATE UNIT WITH DIFFERENT SETTING. 
1 Minute 
0 TO 10 MINUTES 
IN 0.5 MINUTE 
INCREMENTS 
 
Select the length of time unit remains in low speed 
before transitioning to high speed. 
This feature is not supported for the Vector 1550 
model at this time. 
STANDARD = The microprocessor is set to control 
trailer refrigeration operation. 
RAIL = Not recommended for Vector MT 
-12° to + 0°C  
(-21.6° to 0°F) 
(in 0.5°F or °C in-
crements) 
DEFAULT:  
-6°C (-10.8°F) 
Value to be used to calculate the lowest allowable 
supply air temperature, when in Start/Stop Operation, 
in accordance with the formula "Set Point + this value 
= coldest allowable supply air temperature". For ex-
ample, if the set point is 2°C and the Configuration 
value is set at -6°C the calculation is 2 + (-6) = -4°C 
lowest allowed supply air temperature. 
SUPPLY AIR LIMIT FOR CONTIN-
UOUS 
-12° to + 0°C  
(-21.6° to 0°F) 
(in 0.5°F or °C in-
crements) 
DEFAULT:  
-5°C (-9.0°F) 
Value to be used to calculate the lowest allowable 
supply air temperature, when in Continuous Opera-
tion, in accordance with the formula "Set Point + this 
value = coldest allowable supply air temperature". For 
example, if the set point is 2°C and the Configuration 
value is set at -6°C the calculation is 2 + (-6) = -4°C 
lowest allowed supply air temperature. 
When active, this logic indicates if temperature limits 
regulating the exit of pulldown mode are modified or 
not. 
YES = Requires the unit to remain in pulldown until 
the control temperature is +/- 0.2°C (+/- 0.36°F) of 
setpoint 
NO = Normal unit operation. 
Unit Family types, 
and then configura-
ble numbers 
Indicates to the controller the model number of the 
unit. Scroll to the Vector Family entries and select the 
model number from the Model/Serial Number name-
plate. 
The unit S/N may be entered. This may be up to 
10 characters long. Numbers, Letters, and a space 
are available by scrolling through the available list. 
The ID # may be entered. This may be up to 
10 characters long. Numbers, Letters, and a space 
are available by scrolling through the available list. 
ENGINE COOLANT RESTART 
VALUE 
YES = When alarm AL11 has been triggered three 
times in the last two hours of engine operation AL21 
(Technician Reset Required) will be triggered. 
NO = AL21 will not be triggered. 
ENGINE OIL PRESSURE RESTART 
VALUE 
YES = When alarm AL12 has been triggered three 
times in the last two hours of engine operation AL21 
(Technician Reset Required) will be triggered 
NO = AL21 will not be triggered.