2. In this screen you will assign Relays to any
and all of the air inlets connected to the Control.
3. Select Sidewall Inlet
Once you enter in the Open relay number the Control
will automatically enter the Close relay.
Two inlet machines can be assigned to the Sidewall
inlet output. Both machines will be given an open or
close signal at the same time.
Note. The Open and Close outputs must always be side by side on the same relay row.
4. Select the Control tab and choose Calculated or Fixed
Anticipation.
Calculated Inlet Anticipation– The Control determines
the amount of time the Inlets will open prior to the Fans
assigned to the Minimum Ventilation timer turn on at a
given static pressure control limits. (Screen not shown)
Fixed Inlet Anticipation- The amount of time the Inlets
will open prior to the Fans assigned to the Minimum Ven-
tilation timer turn on.
Open Relay Number
Close
Relay Number