1. Use the Back button to get to the Setup/Out-
puts screen and push the Tunnel Inlet Button.
2. When you enter in the Open relay number
the Control will automatically enter the Close
relay.
Up to four machines can be assigned to the
Tunnel inlet output. All machines will be giv-
en an open or close signal at the same time.
Note. The Open and Close outputs must al-
ways be side by side on the same relay row.
Open Relay Number
3. Press the Control Tab
4. These numbers are needed for proper
Mode transitions. (Power to Tunnel and
Tunnel to Power).
Full Movement
Measure the full movement of the Curtain or
Tunnel door and enter that number in the FULL
Movement edit box.
Tunnel Speed
With a closed inlet measure 18 inches of the tun-
nel curtain or door movement. Toggle the open
relay switch to the Manual position.
Time how long it takes to move the the Inlet 18
inches. Enter that number in to the Tunnel
Speed edit box.