EN-17
EN
Cooling:
Fig.8
Air quality regulation setpoint
Maximum flow rate value of supply air fan for air quality control
Indication of the operating mode for T° regulation in "Energy optimisation" mode Level 1 access
Return air Cooling 25.0°c
Comfort Cooling (Return or Ambient air) temperature control setpoint monitored (0 to 50.0°C)
Cooling Eco (Return or Ambient air) temperature control setpoint monitored (0 to 50.0°C)
Return air Heating 23.0°c
Heating Comfort (Return or Ambient air) temperature control setpoint monitored (0 to 50.0°C)
Heating Eco (Return or Ambient air) temperature control setpoint monitored (0 to 50.0°C)
Indication of the control state for the monitored temperature
Indication of the operating mode for T° regulation in "Energy optimisation" mode Level 1 access
Supply air Cooling 16.0°c
Cooling Comfort Supply air temperature control setpoint (Regulated T° ≠ Supply air) (0 to 50.0°C)
Cooling Eco Supply air temperature control setpoint (Regulated T° ≠ Supply air) (0 to 50.0°C)
Supply air Heating 26.0°c
Heating Comfort Supply air temperature control setpoint (Regulated T° ≠ Supply air) (0 to 50.0°C)
Heating Eco Supply air temperature control setpoint (Regulated T° ≠ Supply air) (0 to 50.0°C)
Cooling supply air setpoint
Comfort: 16°C
Eco: 18°C