EN-43
EN
4 Replacing the lithium battery
The lithium battery must be replaced by the customer when the notification alarm appears, approximately 10 years
after the unit is commissioned on site.
Once the replacement has been carried out, do not forget to reset the battery check (screen tp1)
5 Supervision
The controller may be connected to a local or remote supervision PC or to most types of CMS (Modbus, Lonworks,
KNX). For the listed functions to be used, optional cards (Rs485, KNX, LON, pCO Web) or gateways (devices able to
interpret various communication protocols) must be installed
NOTE:
If using a communication bus, the routing and processing of the available data are not provided by the manufacturer.
They must be provided by the installer, and require the involvement of an integrator.
5.1 CMS
Various communication standards can be used to connect with a CMS. Expansion boards are inserted in the "Serial
Card" port on the controller.
Modbus
®
RTU: insert the RS485 expansion board and connect it as instructed in the manual. Validating the protocol
on the user terminal (screen g1):
- Protocol MODBUS RTU
- Speed ---- bds (Set in accordance with the CMS speed)
- Address 001 (Different to 0)
Modbus
®
TCP: insert the pCo Web card and connect it as instructed in the manual. Validating the protocol on the user
terminal (screen g1):
- Protocol MODBUS TCP
- Speed 19200 bds (Obligatory)
- Address 001 (Different to 0)
LonWorks
®
: insert the expansion board ((type FTT-10A)) and connect it as instructed in the manual. Validating the
protocol on the user terminal (screen g1):
- Protocol LON
- Speed 4800 bds (Obligatory)
- Address 001 (Obligatory)
KNX
®
: insert the expansion board and connect it as instructed in the manual. Validating the protocol on the user
terminal (screen g1):
- Protocol KNX
- Speed 9600 bds (Obligatory)
- Address 001 (Obligatory)
5.2 The datapoint database
The unit comes with a communication database that includes the most important datapoints for the program, from the
values of the sensors to the parameters displayed in the masks. The database contains three types of datapoint:
digital datapoints, integer datapoints and analogue datapoints. The tables below list the names of these datapoints,
their addresses and types (read-only (R) or read/write (R/W)).