EN-18
Pre-heating temperature 2.0°c
Electric pre-heater stages starting-up temperature in the duct (-5 to 50.0°C)
Control setpoint in mode "Morning heating" mode (0 to 50.0°C)
Unit reactivation setpoint in "Standby" mode (0 to 50.0°C)
Antifreeze prot. temp 2.0°c
Coil antifreeze protection temperature setpoint (0 to 50.0°C)
Control setpoint in mode "Night cooling" mode (0 to 50.0°C)
Supply air fan flow regulation setpoint for night cooling
Return air fan flow regulation setpoint for night cooling
Heat exchanger frost risk detection temperature setpoint (-10.0 to 50.0°C)
Operating limit temperature for the plate heat exchanger (bypass open) (-20.0 to 50.0°C)
Wheel heat exchanger operating limit temperature setpoint (-40.0 à 50.0°C)
Min. temperature setpoint value regulated via the room terminal.
Max. temperature setpoint value regulated via the room terminal.
2.3 Machine parameters menu
This menu is Level 3 access
Level 2 access This screen is used to configure the criticality of the faults managed by the regulating controller.
If a fault is shown as "Danger" the unit will be shut off. If the fault is shown as "Maintenance", only an alarm
Criticality of faults 1 to 9
Criticality of faults 10 to 19
Criticality of faults 20 to 29
List of faults:
Supply air filter clogged
Return air filter clogged
Frost on heat exchanger - Fresh air temperature check
Heat recovery unit frosted – Clogging detection
Rotary heat exchanger check