EN-24
2.4 Adjustment parameters menu
Controller language selection (French, English, German, Spanish, Italian, Dutch)
Level 1 access
Clock time correction value
Clock date correction value
Proportional band for monitored temperature regulation in cooling mode
Deadband value for monitored temperature regulation in cooling mode
Integration time and derivative time for monitored temperature regulation in cooling mode
Proportional band for monitored temperature regulation in heating mode
Deadband value for monitored temperature regulation in heating mode
Integration time and derivative time for monitored temperature regulation in heating mode
Value for the Return or Ambient air T° control differentials in "Energy optimisation" mode
In cooling mode In heating mode
Fan management:
- Qv csts, indep: Constant flow rates and independent setpoints
- Intake pressure: Constant Supply air duct pressure and identical fan speeds
- Intake+return air pressure: Constant Supply air duct pressure + constant Return air duct pressure and independent fan
speeds.
- Qv csts, prop/intro: Constant flow rates and Return air flow rate setpoint proportional (multiplied by M factor) to the Supply
air flow rate setpoint
- Qv csts, prop/extra: Constant flow rates and Supply air flow rate setpoint proportional (multiplied by M factor) to the Return
air flow rate setpoint
- Qv/Tregul, prop: Constant flow rates and independent setpoints, but based on the difference between the measurement
and regulated temperature setpoint (as per Fig. 3, page 26)
When operating with constant pressure on both air flows, there is no balancing of the two flow rates. It is the set-up technician's
responsibility to adjust the minimum opening settings for the duct dampers in order to ensure the statutory recirculation of air on site.
Duct P sensor: