2.4 Adjustment parameters menu
lg
Level 1 access
Language ------------
Controller language selection (French, English, German, Spanish, Italian, Dutch)
Setting t0
of the clock
Level 1 access
Time -- :--
Clock time correction value
Date --/--/--
Clock date correction value
Supply air p1
Level 2 access
CLG band 0005.0
Proportional band for monitored temperature regulation in cooling mode
Cooling DB 00.0
Deadband value for monitored temperature regulation in cooling mode
T I 0150s T D 0000s
Integration time and derivative time for monitored temperature regulation in cooling mode
HTG band 0005.0
Proportional band for monitored temperature regulation in heating mode
Heating DB 00.0
Deadband value for monitored temperature regulation in heating mode
T I 0150s T D 0000s
Integration time and derivative time for monitored temperature regulation in heating mode
Return air p2
Level 2 access
Differential
Value for the Return or Ambient air T° control differentials in "Energy optimisation" mode
Cooling Heating
In cooling mode In heating mode
0.0 0.0
p3
Level 2 access
Fan management
--------
Duct P sensor -----
Compensated Qv ----
Compensated T° ----
Free Cooling ----
Fire ----
Fan management:
- Qv csts, indep: Constant flow rates and independent setpoints
- Intake pressure: Constant Supply air duct pressure and identical fan speeds
- Intake+return air pressure: Constant Supply air duct pressure + constant Return air duct pressure and independent fan
speeds.
- Qv csts, prop/intro: Constant flow rates and Return air flow rate setpoint proportional (multiplied by M factor) to the Supply
air flow rate setpoint
- Qv csts, prop/extra: Constant flow rates and Supply air flow rate setpoint proportional (multiplied by M factor) to the Return
air flow rate setpoint
- Qv/Tregul, prop: Constant flow rates and independent setpoints, but based on the difference between the measurement
and regulated temperature setpoint (as per Fig. 3, page 26)
When operating with constant pressure on both air flows, there is no balancing of the two flow rates. It is the set-up technician's
responsibility to adjust the minimum opening settings for the duct dampers in order to ensure the statutory recirculation of air on site.
Duct P sensor: