EN-16
Supply air
Upper limit 26.0°c
Upper limit for calculated Supply air T° setpoint
Lower limit 16.0°c
Lower limit for calculated Supply air T° setpoint
2.2.1 Supply air T° setpoint calculation in "Precision" mode
Fig.4
Fig.5
2.2.2 Supply air T° setpoint calculation in "Energy optimisation" mode
Return air or room temp. control
Fig.6
Heating:
Fig.7
lower limit
upper limit
°C
X2
X1
Return T°
Ambient T°
Setpoint
Calculated Supply air T°
setpoint
Setpoint
°C
setpoint
Cooling requirement (%)
0
100
50
band
Heating requirement (%)
band
Return T°
Ambient T°
Heating
authorised
Heating
setpoint
Comfort: 23°C
Eco: 18°C
Cooling authorised
Deadband
Cooling
setpoint
Comfort: 25°C
Eco: 27°C
°C
100
50
Heating requirement (%)