6 Table of alarms
* All possible options are covered by this table
Alarm
Source
Causes
Solutions
Supply air filter
clogged
Supply air filter fouling
pressure sensor
0-1000 Pa
B1
- Filter too dirty
- Replace filter
Supply air filter
dirty
- Filter fouled
- Clean or replace filter
Frosted heat
exchanger; operating
temperature too low
Fresh air temperature
sensor
B5 or B9
- Heat exchanger fouled
- Heat exchanger frosted
- Clean the heat exchanger
- See causes
Heat recovery unit
frosted
Fouling level
detection
Heat exchanger fouling
pressure sensor
0-1000 Pa
B6
- Heat exchanger fouled
- Heat exchanger frosted
- Clean the heat exchanger
- See causes
Return air filter
clogged
Return air filter fouling
pressure sensor
0-1000 Pa
B8
- Filter too dirty
- Replace filter
Return air filter
dirty
- Filter fouled
- Clean or replace filter
Supply air fan motor
assembly protection
Supply air fan monitoring
ID2
- Rotor blocked
- Phase check
- Voltage too low
- Thermal protection
- Short-circuit
- See causes
- Check wiring
- Monitor supply voltage
- Monitor starting current
- See causes
Return air fan motor
assembly protection
Return air fan monitoring
ID3
- Rotor blocked
- Phase check
- Voltage too low
- Thermal protection
- Short-circuit
- See causes
- Check wiring
- Monitor supply voltage
- Monitor starting current
- See causes
Rotary heat
exchanger
Heat exchanger control
unit
ID7
- Controller fault
- See causes
Electric pre-heater
Safety thermostats and
circuit breaker QR1
ID4
- Thermostats fault
- Circuit breaker (QR1)
- Current too high
- Short-circuit
- See causes
- Reset or replace
- Monitor current
- See causes
Electric heater
Safety thermostats and
circuit breaker QR2
ID5
- Thermostats fault
- Circuit breaker (QR2)
- Current too high
- Short-circuit
- See causes
- Reset or replace
- Monitor current
- See causes
Humidifier
Tank
Water
ID10
- Cylinder dirty
- Water insufficiently
conductive
- Change cylinder
- Add a handful of salt
Coil 1 pump
Pump 1 monitoring
ID11
- Electrical protection fault
- No water flow
- See causes
- See causes
Coil 2 pump
Pump 2 monitoring
ID12
- Electrical protection fault
- No water flow
- See causes
- See causes
Clock battery must
be replaced
Controller
- Flat battery
- Replace the battery