EN-27
EN
Fig. 3.bis
p10
Screen appears if the "Morning heating" function is used in a time program (Level 2 access)
Mixing opening
in "Morning heating" mode
095%
Opening value of mixing damper in "Morning heating" mode
p11
Screen appears if the "ECO recirculation" function is used in a time program (Level 2 access)
Mixing opening
in "ECO Recirculation" mode
095%
Opening value of mixing damper in "ECO Recirculation" mode
Supply air p14
Level 3 access
Fan band 1400.0
Supply air fan flow control proportional band
Fan IT 0008s
Supply air fan flow control integration time
Start speed 0.0%
Supply air fan speed at the end of the soft start
Return air
Fan band 1400.0
Return air fan flow control proportional band
Fan IT 0008s
Return air fan flow control integration time
Start speed 0.0%
Return air fan speed at the end of the soft start
6
4
Fresh air T°
Comfort
Fault-
tolerant
Supply air flow rate