EN-29
EN
p17
Level 3 access
FC offset -3.0°c
Outdoor T° offset from regulated T° for Free Cooling authorisation
Lower limit 15.0°c
Outdoor temperature low limit in free cooling and night cooling mode
p22
Level 3 access
Setpoint min. threshold
Filter fouling level
supply air ----Pa
Supply air filter fouling minimum threshold (0-100 Pa)
Setpoint min. threshold
Filter fouling level
return air ---Pa
Return air filter fouling minimum threshold (0-100 Pa)
p25
Level 2 access
Compensated duct P -
Without, With (Pressure compensation as per Fig. 2b, page 26)
FA flow rate down -
Without, With (Fresh air flow rate downgraded as per Fig. 3b, page 26)
Calibration ca1
Level 3 access
Return air 00.0°c
Calibration of the return air or fresh air temperature sensor
Supply air 00.0°c
Calibration of the supply air temperature sensor
Fresh air 00.0°c
Calibration of the fresh air or return air temperature sensor
Air quality 0000ppm
Calibration of air quality sensor
Duct 00.0°c
Calibration of the supply air duct remote temperature sensor
Calibration ca1b
Access Level 3
Press the prog button from screen ca1
Pressure sensor
calibration NO
Manual calibration of pressure sensors. Warning: the fans must be completely stopped before
using this function.