EN-49
EN
Register
hex. no.
Register
decimal
no.
Description Format Type Values
0x463 1123 Electric pre-heater Boolean Read-only
0 = Fault
1 = No fault
0x464 1124 Electric heater Boolean Read-only
0 = Fault
1 = No fault
0x465 1125 Hydraulic coil 1 pump monitoring Boolean Read-only
0 = Fault
1 = No fault
0x466 1126 Hydraulic coil 2 pump monitoring Boolean Read-only
0 = Fault
1 = No fault
0x467 1127 Humidifier monitoring Boolean Read-only
0 = Fault
1 = No fault
0x468 1128 Electric heater load shedding control Boolean Read-only
0 = Authorised
1 = Prohibited
0x469 1129 Remote control or Presence detection Boolean Read-only
0 = Off
1 = On/Presence
0x474 1140 Intake fan control Integer Read-only
value in % x10
0x475 1141 Exhaust fan control Integer Read-only
value in % x10
0x476 1142 Hydraulic coil 1 valve control Integer Read-only value in % x10
0x477 1143 Hydraulic coil 2 valve control Integer Read-only value in % x10
0x478 1144 Heat exchanger wheel speed control Integer Read-only value in % x10
0x47B 1147 Heat exchanger bypass damper opening value Integer Read-only value in % x10
0x47C 1148 Heat exchanger bypass control state Integer Read-only 0: no control
1: open
2: closed
0x47D 1149 "Danger" fault summary relay Boolean Read-only
0 = No fault
1 = Fault
0x47E 1150 "Maintenance" fault summary relay Boolean Read-only
0 = No fault
1 = Fault
0x483 1155 Unit insulation damper control Boolean Read-only
0 = Damper closed
1 = Damper open
0x484 1156 Control 1 for the electric heaters Boolean Read-only
0 = Off
1 = On
0x485 1157 Control 2 for the electric heaters Boolean Read-only
0 = Off
1 = On
0x48A 1162 Hydraulic coil 1 pump control Boolean Read-only
0 = Off
1 = On
0x48B 1163 Hydraulic coil 2 pump control Boolean Read-only
0 = Off
1 = On
0x48D 1165
External heat production control (boiler or heat
pump)
Boolean Read-only
0 = Off
1 = On
0x48E 1166 Humidifier operation authorisation Boolean Read-only
0 = Off
1 = On
0x491 1169 Mixing damper opening value Integer Read-only
value in % x10
0x492 1170 Mixing damper control state Integer Read-only
0: no control
1: open
2: closed
0x49E 1182
Calculated regulation setpoint for the supply air
temperature
Integer Read-only