EN-56
Bit 3 = Sensor B4
Bit 4 = Sensor B5
Bit 5 = Sensor B6
Bit 6 = IAQ sensor
Bit 7 = Sensor B8
Bit 8 = Sensor B9
Bit 9 = Hydraulic coil 1 pump
Bit 10 = Hydraulic coil 2 pump
Unit On/Off command via CMS
Unit On/Off command return via
CMS
Air supply fan monitoring
Return air fan monitoring
Electric pre-heater safety
monitoring
ControleBattElecPre DPT_Switch 1.001
OUT
5
COIL
Electric heater safety monitoring
Rotary heat exchanger check
Presence detection or remote
control
DetectionCAD DPT_Switch 1.001
OUT
10
COIL
Damper control (frost protection or
insulation)
Registre DPT_Switch 1.001
OUT
19
COIL
External generator control (boiler
or heat pump)
Generateur DPT_Switch 1.001
OUT
21
COIL
Electric heater stage 1 control
Electric heater stage 2 control