CHAPTER 8
Power Cabling
This chapter describes how to connect -48 VDC power feeds to the Power Filter Units (PFUs) on the ASR
5500 chassis.
The -48 VDC Battery Return (BR) input terminals to the PFUs are not connected to the equipment frame
(chassis) are treated as Isolated DC returns (DC-I) in compliance with GR-1089-CORE (sec.9.8.3).
Important
This chapter includes the following sections:
Power Considerations, page 77
Internal Power Planes, page 78
Power Cable Requirements, page 81
Connect Power Feeds to the PFUs, page 83
Power Considerations
Each chassis supports up to eight -48 VDC, 80-amp power feeds, four per PFU. Each feed consists of a supply
and return cable.
The power source must be a UL/CSA listed device with a regulated output no greater than -60VDC.Important
Typically, the DC power feeds are fed from a power distribution frame (PDF) to a power distribution panel
(PDP) at the rack.
The DC power Battery Return (BR) or positive terminal, must be grounded at the source end (power feed
or mains power end).
Important