42
ASW sensors are wall-mounted temperature sensors
for use with the MPC controller with Water-to-Air units.
The ASW is available in 3 different models to allow for
application exibility. Features such as room temperature
sensing, digital LCD readout, set point adjustment,
override pushbutton, heat pump reset, lockout
recognition, fault type, LED indicator, cosmetics and
occupancy status can be supplied by the different types
of ASW wall sensors. The ASW wall mounted sensors
are low prole, which provides a distinguished look for
building architects and engineers.
The three different types of ASW wall sensors feature
easy to use analog to digital connections on the MPC.
With only 4 to 5 wire connections, the eld technician
can easily troubleshoot the ASW to determine if it is
operating properly.
The ASW15 displays zone temperature, heating setpoint,
cooling set point. And if so equiped will display sensed
values of humidity, CO2 and VOC's.
MPC Wall Sensors
Room temperature is measured using a 10k thermistor
and can be indicated on an easy to read LCD display
(with display only wall sensor). The set point adjust is a
slide potentiometer which provides an analog output and
is available with a Warm/Cool legend imprinted on the
unit's base. The override is a momentary, normally open,
push contact.
ASW wall sensors are suitable for direct-wall mount or
electrical box mounting. Terminations are easily made
at the screw terminal block located on the wall sensor
back plate.