InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013
This setpoint adjusts the gain factor (P-factor) of the frequency control PI
loop. The integration factor (I-factor) for the frequency loop is adjusted by the
setpoint Freq int.
FREQ GAIN AND FREQ INT SETPOINTS ARE ACTIVE DURING:
synchronization between “left” and “right” buses
NOTE:
When this setpoint is set to zero, the corresponding control loop is switched
OFF.
NOTE:
See the chapter Regulation loops overview for general information about
regulation loops and their adjustment.
12.2.9.6 Setpoint: Freq int
This setpoint adjusts the relative integration factor (I-factor) of the frequency
control PI loop. The gain factor (P-factor) for the frequency loop is adjusted
by the setpoint Freq gain.
FREQ GAIN AND FREQ INT SETPOINTS ARE ACTIVE DURING:
synchronization between “left” and “right” buses
NOTE:
See the chapter Regulation loops overview for general information about
regulation loops and their adjustment.