EasyManuals Logo

ComAp InteliLite 4 AMF 20 User Manual

ComAp InteliLite 4 AMF 20
620 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #478 background imageLoading...
Page #478 background image
InteliLite4 AMF20 Global Guide
478
This output controls the fuel solenoid valve. The Fuel Solenoid output has two different behaviors
depending on engine type – gas or diesel. This setting is done by Fuel Solenoid (page 225) setpoint in
Engine Settings group.
Diesel:
The output is activated before binary output STARTER (PAGE 501).The lead time is adjusted by setpoint
Fuel Solenoid Lead (page 235).
Image 8.32 Fuel Solenoid 1
Image 8.33 Fuel Solenoid 2
The output is deactivated when:
Emergency Stop comes
Cooled Gen-set is stopped
In pause between repeated starts