The gen-sets may be started in MAN mode but they will not start in
AUT mode due to MGCB not closing.
The MGCB can't be closed (if there is voltage on the bus).
The message OfL StartBlck is present in the alarm list (see the alarm
output OfL StartBlck).
NOTE:
See table with examples in the description of the setpoint MFStart enable.
11.2.1.25 Setpoint: Synchro enable
Group
Process Control
Range [units]
NONE, FORWARD, REVERSE, BOTH [-]
Related FW
standard v3.1.0
Force value
possible
YES
Description
The setpoint is used for enable/disable forward and reverse synchronization.
NONE: No synchronizing is enabled.
ONLY IN MGCB APPL: FORWARD: MGCB synchronizing is
enabled.
REVERSE: MCB synchronizing is enabled.
ONLY IN MGCB APPL: BOTH: MGCB and MCB synchronizing are
enabled.
NOTE:
Although synchronizing of the particular breaker is disabled the breaker can
be closed to a "dead" (voltage-free) bus.
NOTE:
See table with examples in the description of the setpoint MFStart enable.
11.2.1.26 Setpoint: MFStart enable
Group
Process Control
Range [units]
NO, YES [-]
Related FW
standard v3.1.0