InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
197
ENABLED
The communication port COM1 is redirected to the
integrated RS485(1) converter. The RS232(1) connector
has no function and the external display interface is not
available.
DISABLED
The communication port COM1 is present at the RS232(1)
connector and the RS485(1) connector is used for the
external display interface.
NOTE:
The redirection is applied only for DIRECT, MODBUS and ECU-LINK modes.
See the setpoint RS232(1) mode.
NOTE:
This setpoint must be set to DISABLED at controllers that do not have
internal display. i.e. InteliVision-5 or InteliVision-8 is connected to the
RS485(1) terminals.
11.2.3.11 Setpoint: RS485(2) conv.
Group
Comms settings
Range [units]
DISABLED, ENABLED [-]
Related FW
standard v3.1.0
Description
This setpoint selects function of the built-in RS485(2) converter.
ENABLED
The communication port COM2 is redirected to the
integrated RS485(2) converter. The RS232(2) connector
has no function.
DISABLED
The communication port COM2 is present at the RS232(2)
connector.
NOTE:
The redirection is applied only for DIRECT, MODBUS and ECU-LINK modes.
See the setpoint RS232(2) mode.
NOTE:
This setpoint has no function for IG-NT(C)-BB and IS-NTC-BB as this

Table of Contents