InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
The communication port COM1 is redirected to the
integrated RS485(1) converter. The RS232(1) connector
has no function and the external display interface is not
available.
The communication port COM1 is present at the RS232(1)
connector and the RS485(1) connector is used for the
external display interface.
NOTE:
The redirection is applied only for DIRECT, MODBUS and ECU-LINK modes.
See the setpoint RS232(1) mode.
NOTE:
This setpoint must be set to DISABLED at controllers that do not have
internal display. i.e. InteliVision-5 or InteliVision-8 is connected to the
RS485(1) terminals.
11.2.3.11 Setpoint: RS485(2) conv.
This setpoint selects function of the built-in RS485(2) converter.
The communication port COM2 is redirected to the
integrated RS485(2) converter. The RS232(2) connector
has no function.
The communication port COM2 is present at the RS232(2)
connector.
NOTE:
The redirection is applied only for DIRECT, MODBUS and ECU-LINK modes.
See the setpoint RS232(2) mode.
NOTE:
This setpoint has no function for IG-NT(C)-BB and IS-NTC-BB as this