InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
This setpoint is used to adjust the port, which is used for ethernet connection
to a PC with any of ComAp PC program (i.e. InteliMonitor, GenConfig). This
setpoint should be adjusted to 23, which is the default port used by all
ComAp PC programs. A different value should be used only in special
situations as e.g. sharing one public IP address among many controllers or to
overcome a firewall restrictions.
11.2.3.23 Setpoint: AirGate
This setpoint selects the ethernet connection mode.
This is a standard mode, in which the controller listens to
the incoming traffic and answers the TCP/IP queries
addressed to him. This mode requires the controller to be
accessible from the remote device (PC), i.e. it must be
accessible at a public and static IP address if you want to
connect to it from the Internet.
This mode uses the "AirGate" service, which hides all the
issues with static/public address into a black box and you
do not need to take care about it. You just need only a
connection to the Internet. The AirGate server address is
adjusted by the setpoint AirGate addr.
11.2.3.24 Setpoint: AirGate IP
This setpoint is used for entering the domain name or IP address of the
AirGate server. Use the free AirGate server provided by ComAp at address
airgate.comap.cz if your company does not operate it's own AirGate server.
11.2.3.25 Setpoint: SMTP authent