InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
218
11.2.6.18 Setpoint: ROCOF df/dt
Group
Mains protect
Range [units]
0.1 .. 10.0 [Hz/s]
Related FW
standard v3.1.0
Description
This setpoint adjusts the trip level for ROCOF protection (Rate Of Change Of
Frequency). The "filtration level" for the ROCOF protection is adjusted by
setpoint ROCOF Win.
NOTE:
If measured value of df/dt exceeds ROCOF df/dt, ROCOF protection is
activated. The message ROCOF is writen in history of controller and
corresponding logical binary output is activated ROCOF Trp. Value of df/dt is
evaluated from mains voltage.
NOTE:
To activate or deactivate ROCOF protection, please use ROCOF prot.
Choose proper breaker which will be opened if ROCOF protection activates
by adjusting setpoint VS/ROCOF CBsel.
11.2.6.19 Setpoint: Mains V unbal
Group
Mains protect
Range [units]
0 .. 200 [%]
Related FW
standard v3.1.0
Description
This setpoint defines the threshold level for Mains voltage unbalance
protection. The voltage unbalance is calculated as a maximum difference
between phase voltages. This protection is evaluated with delay given by
Mains Vunb del.
11.2.6.20 Setpoint: Mains Vunb del
Group
Mains protect
Range [units]
0.0 .. 600.0 [s]
Related FW
standard v3.1.0
Description
This setpoint adjusts delay for mains voltage unbalance alarm (see Mains V
unbal).