NOTE:
Repeated pressing of button during the closed period
causes issuing another puls to be generated from the
moment of button pushing.
14.2.1.100 Binary output: ROCOF Trp
Related FW
standard v3.1.0
Description
The output closes if the ROCOF protection gets active. The output stays
closed for 3s, then opens again.
14.2.1.101 Binary output: PeakShaveAct
Related FW
standard v3.1.0
Description
Binary output is active when the gen-set is running (in SPtM application) or
gen-set group is activated by InteliMains due to Peak Shaving or Peak kVA
Shaving (dependence on parameters PeakLevelStart, PeakLevelStop,
PeakAutS/S del, Peak kVA Start, Peak kVA Stop, PeakKVAS/S del in
ProcessControl group).
14.2.1.102 Binary output: Initialized
Related FW
standard v3.1.0
Description
This LBO indicates that the controller finished the reboot after the restart. It
can be used in internal PLC for blocking some binary inputs to avoid the
hazards after restart of the controller.
14.2.1.103 Binary output: Start Blocked
Related FW
standard v3.1.0
Description
Activation of this logical binary output indicates that the start of the engine is
blocked. This can be caused by conditions given by setpoints in
ProcessControl group (Island enable, ParalEnable, Synchro enable, MFStart
enable, MGCBparalClose - where aplicable).
EXAMPLE:
The start of the gen-set is blocked when Mains is not OK and Island enable is
set to NO. Therefore this output is activated and letting you know that the
gen-set will not start because the island operation is not allowed.