12.1.1.31 Value: Mains curr L3
Group
Mains values
Units
A
Related FW
standard v3.1.0
Description
Mains current in phase L3.
NOTE:
The ratio between the current measured at the input terminals and the
displayed current is adjusted by the setpoints MainsCTprim and MainsCTsec.
12.1.1.32 Value: Mains V unbal
Group
Mains values
Units
%
Related FW
standard v3.1.0
Description
Mains voltage unbalance. The value is calculated as maximal difference of
two phase voltages at one moment and expressed in % of the nominal
voltage.
NOTE:
This value can be used for creating the Mains voltage unbalance protection
using the "universal analog protections".
12.1.1.33 Value: Mains I unbal
Group
Mains values
Units
V
Related FW
standard v3.1.0
Description
Mains current unbalance. The value is calculated as maximal difference of
two phase currents at one moment and expressed in % of the nominal
current.
NOTE:
This value can be used for creating the Mains current unbalance protection
using the "universal analog protections".