13.2.1.95 Binary input: Force block 1
Related FW
standard v3.1.0
Description
This is one of three binary inputs used for user-defined blocking of
protections. If the input is active, all the protections that have Protection block
type configured as Force block 1 block type are blocked (i.e. temporarily
disabled).
13.2.1.96 Binary input: Force block 2
Related FW
standard v3.1.0
Description
This is one of three binary inputs used for user-defined blocking of
protections. If the input is active, all the protections that have Protection block
type configured as Force block 2 block type are blocked (i.e. temporarily
disabled).
13.2.1.97 Binary input: Force block 3
Related FW
standard v3.1.0
Description
This is one of three binary inputs used for user-defined blocking of
protections. If the input is active, all the protections that have Protection block
type configured as Force block 3 block type are blocked (i.e. temporarily
disabled).
13.2.1.98 Binary input: Lang sel int A
Related FW
standard v3.1.0
Description
This is one of three binary inputs Lang sel int A, Lang sel int B, Lang sel int
C, used for selecting language of the built-in IG-NT terminal (display). As the
IS-NT does not have built-in terminal, this input is assigned to the terminal
(display) #1, which is supposed to be directly attached to the controller or
mounted close to it.
NOTE:
Using these inputs for language selection is an option only. If the inputs are
not configured, the language can be selected using the menus on the
terminal.
ENCODING TABLE
LANGUAGE INDEX
INPUT A
INPUT B
INPUT C
0
0
0
0

Table of Contents