Modbus address
01
Diagnose pgm
(ENTER=Entry)
erase history
(ENTER=Entry)
– Demineralization mode
Enabling(“on”)ordisabling(“off”)theDemineralizationmode.
Note:Enable thedemineralizationmode ifyouare usingsoftenedwater or
waterwithahighconductivity.
Factory setting: on
Available settings: on(Demineralizationmodeenabled)
off(Demineralizationmodedisabled)
Note:TheDemineralizationmodeushesthesteamcylinderwithinanhour
afterapresetnumberofscumdetectionshastakenplace(seenextparameter
“Demineralizationdelay”).Thispreventstheformationofscum.
– Demineralization delay
Setthedemineralizationdelayafterwhichatime-controlledushingcycle
willbeinitiated.
Note: This menu item is available only if the Demineralization mode is
enabled.
Factory setting: 3
Setting range: 1…9
Note: The demineralization delay determines the number of times the
maximumlevel(scumdetection)maybereachedbeforeatime-controlled
ushingcyclewilltakeplace.
– Modbus address
Setthemodbusaddressforunitswithbuilt-intelemonitoringinterfaceorbuilt-in
RS232/RS485serialinterface.
Factory setting: 1
Setting range: 1...16
Note: Detailed information about the telemonitoring interface (installation,
correctaddressingofunitsinacluster)andtheserialinterface(installation,
conguration)can be found in theseparatemanuals that are suppliedwith
these options.
– Diagnostic program
The diagnostic program simulates various operating conditions of the steam hu-
midier.However,thediagnosticprogramrequiresin-depthknowledgeofpar-
ticular internal functions of the unit. Therefore, the diagnostic program should
beusedbyCondairservicetechniciansonly.
– Error history
Numericalcodesofthelast4errorsencountered(oldestentryfarleft).
Note: For detailed information on the meaning of particular error numbers
please refer to chapter 6.7.
– Delete fault history
Faulthistoryisdeleted.Anappropriatemessageappearsfollowingthedele-
tion.
demineral. delay
3
faulthistory
. / . /9.A/9.A
demineral. mode
on