– Proportional range(P-band)oftheinternalPIcontroller
Proportional range of the internal PI controller in %.
Note: This menu option is available only if the internal PI controller is ac-
tive.
Factory setting: 30 %
Setting range: 4…100 %
Note: The P-Range is used to smooth the control characteristic. Increasing
the P-Range boosts the smoothing applied to the control characteristic.
However,thiscausesapermanentdeviation,proportionaltothebandwidth
of the P-Range.
– Integral time of the internal PI controller
Integral time of the internal PI controller in minutes.
Note: This menu option is available only if the internal PI controller is ac-
tive.
Factory setting: 10 Minutes
Options: off(000/integraltimedisabled),2 - 100 Minutes
Note:Theintegraltimesettingdeterminestheperiodallowedtoreachthe
nominal humidity. Setting the integral time to the optimal value prevents the
control characteristic from overshooting and, at the same time, balances
the permanent deviation caused by the P-Range value.
– Soft start
Enabling(on)ordisabling(off)theSoftstartfunction.
Note:Enablethesoftstartfunctionifyouareusingsoftenedwaterorwater
withahighconductivity.
Factory setting: off
Available settings: on(Softstartenabled),off(Softstartdisabled)
Note:Afterrestartoraftertheunithasbeenidlefor4hours(stand-by)theSoft
startfunctionreducesthehumidicationcapacitytoapresetvalueforaselect-
ableperiod(valuesettingsseeparametersbelow).
– Time limit for Soft start
Select the time limit for the Soft start function in minutes.
Note: This menu item is available only if the Soft start function is enabled.
Factory setting: 30 minutes
Setting range: 1…255 minutes
– Capacity limit for Soft start
SetthecapacitylimitfortheSoftstartfunctionin%ofmaximumhumidica-
tion capacity.
Note: This menu item is available only if the Soft start function is enabled.
Factory setting: 50 %
Setting range: 4…100 %
Integr.time[min]
010
P-band [%]
030
softstart
off
softstart time
30 Min
softst. power
50 %