Description of the menu items on the setting level
Thefollowinglistsallthemenuitemsthatcanbeselectedandchangedafteractivationofthesetting
level.
Language
Dialogue language of the display unit.
Factory setting: depends on the country
Options: german, english, french
Note:Thedisplayunitswitchestotheselectedlanguageimmediatelyafterthe
suitablelanguageoptionhasbeenconrmed.
Capacity limitation
Limitationofthesteamcapacity(in %)inreferencetothemaximumsteam
capacity.
Factory setting: 100 %
Setting range: 10…100 %
Note:Thisparameterisusedtolimitthemaximumperformanceincasethe
steamcapacityexceedsthehumidicationrequiredbyyourinstallation.
Inlet valve correction
Setting the cycle frequency of the inlet valve in % of the standard setting.
Note:ThismenupointisonlygiveninMk5Processunit.
Factory setting: 100 %
Setting range: 70-130 %
Comment:Thewaterfeedquantitycanbereduced(value<100)orincreased
(value>100)withthisparameterinordertobalanceoutvariationsinwater
pressure.
Controller setup
Activation(“on”)/Deactivation(“off”)oftheinternalPIcontroller.
Factory setting: off
Options: on(PIcontrolleractivated),off(PIcontrollerdeactivated)
Note:Theinternalcontrollermustnotbeactivatedifanexternalcontrolleris
connectedtothehumidierbecausetheinternalcontrollerwouldinterpretthe
analogsignaloftheexternalcontrollerastheactualhumidityvaluedetected
byahumidity sensor.Thiswould causetheinternalcontrollerto switchthe
humidierto100%steamcapacityiftheinputsignaldropsto0%which,in
turn,wouldleadtoover-humidication.
Nominal humidity value
Nominal humidity value in % rh.
Note: This menu option is available only if the internal PI controller is ac-
tive.
Factory setting: 45 %rh
Setting range: 10…100 %rh
language
English
power limit [%]
100
controller funct
off
ref.value rh [%]
045
inlet valve cor.
100