59Fault elimination
Warning Fault Message Possible causes Remedy
––– E159
HeatElement2controlrelay Heating element control relay 2 does not work correctly.
Note: The operation of the Condair RM is stopped. After the fault
has been eliminated, the Condair RM must be switched off and on
again.
Heating element control relay 2
on control board blocked.
Contact your Condair represen-
tative.
W163 ––– Cartridge replacement The maintenance counter for replacement of the optional lter
cartridge in the water supply of the Condair RM has elapsed.
Note: The Condair RM continues to work normally.
Optional lter cartridge is
exhausted.
Replace lter cartridge, then
reset the maintenance counter
(see Condair RM operation
manual).
W164 –––
Hardwarereplacement The maintenance counter for replacement of the hardware of the
Condair RM has elapsed.
Note: The Condair RM continues to work normally.
The hardware of the Condair
RM is outdated.
Contact your Condair represen-
tative.
––– E170
Hum.SensoroutofRange The measured humidity is outside the permissible range.
Note: The operation of the Condair RM is stopped. After eliminating
the fault, the Condair RM must be switched off and on again.
Wrong humidity sensor con-
nected.
Check that the correct humidity
sensor is connected.
Humidity sensor not connected
or not correctly connected.
Check/correctly connect the wir-
ing of the humidity sensor.
Incorrect conguration of the
humidity sensor in the control
software.
Check/correctly set the humidity
sensor settings in the control
software.
Humidity sensor defective. Replace humidity sensor.
––– E171
Hum.Sensor
Instable
Measurement of air humidity unstable.
Note: The operation of the Condair RM is stopped. After eliminating
the fault, the Condair RM must be switched off and on again.
Unstable humidity measure-
ment due to manipulation of the
humidity sensor.
Check humidity sensor.
––– E181 Cntr/Demand Input The control or demand signal at the signal input is outside the valid
range.
Note: The operation of the Condair RM is stopped. After eliminating
the fault, the Condair RM must be switched off and on again.
The measured value at the
control or demand signal input
is outside the valid range.
Check the signal input.
––– E200 File System Initialization of the Flash le system failed.
Note: The Condair RM continues to work normally. After eliminating
the fault, the the Condair RM must be switched off and on again to
reset the fault.
A problem occurred during
initialization of the ash le
system.
Contact your Condair represen-
tative.
––– E201 Ethernet Initialization of Ethernet adapter failed.
Note: The Condair RM continues to work normally. After eliminat-
ing the fault, the Condair RM must be switched off and on again to
reset the fault.
A problem occurred during
initialization of the Ethernet
adapter.
Contact your Condair represen-
tative.