Service & Maintenance Manual 3Maintenance
5100614_CFD5000 T - CM4.3_Service & Maintenance Manual_T_EN_2020_E
13
3.4.3.5 Flame Detectors
NOTE!
Use appropriate test equipment, available at your authorised dealer. This is
especially important when testing a detector in a hazardous (Ex-classified)
location/area. See section Approved Test Equipment, page 10.
CAUTION!
For testing a flame detector in a hazardous (Ex-classified) location/area, please
contact Consilium for consultation.
For instructions how to use the test equipment, refer to the data sheet.
DANGER!
Open flame (cigarette lighter) should not be used for testing in explosive areas.
3.4.3.6 Manual Call Points
CS-MCP, CS-MCP RAIL, CS-MCP WP and CS-MCP WP Ex
The call point can be tested with a special key, included in the delivery.
Figure 1. Testing CS-MCP, CS-MCP RAIL, CS-MCP WP and CS-MCP WP Ex
1 Insert the test key.
2 Reset the call point.
3 Release the test key.
4 Check and reset any fault codes generated from the testing.
CS-MCP HD and CS-MCP HD Ex
The call point can be tested with a special key, included in the delivery.