5.7 Handover to the operating
company
Once the test run is finished and the unit operates properly, please
make sure the following is clear for the user:
Fill in the installer setting table (in the operation manual) with the
actual settings.
Make sure that the user has the printed documentation and ask
him/her to keep it for future reference. Inform the user that he can
find the complete documentation on the url as earlier described in
this manual.
Explain the user how to properly operate the system and what he/
she has to do in case of problems.
Show the user what he/she has to do in relation to maintaining the
unit.
Explain the user about energy saving tips as described in the
operation manual.
6 Technical data
Part of the current technical data is available on the regional Daikin-
website (publicly accessible). The complete technical data is
available via the Daikin Business Portal (authentication required).
6.1 Information on the type plate
 6‒1 Type plate
a Device type
b Empty weight
c Total filled weight
d Max. permissible operating pressure PMS (heating)
e Total storage capacity
f Max. permissible operating temperature T
max
g Standby heat loss in 24hours at 60°C (storage tank) Q
st
h Operating pressure of storage water pH
2
O
i Nominal capacity of drinking water
j Max. operating pressure PMW (plumbing)
k Nominal voltage U
l Protection type
m Electrical power input elmax
n Backup heater (optional)
o Backup heater protection class (optional)
p Backup heater fuse (optional)
q Output/backup heater power supply (optional)
To select; 0kW: no/external heat source
r Refrigerant circuit
s Max. operating pressure (refrigerant circuit)
t Total refrigerant charge (for information, see installation
instructions for the outdoor heat pump unit)
u Attention: Flammable refrigerant
v Further information on the refrigerant: See instructions
w Serial number (specify in the event of complaints or
inquiries)
x Date of production
6.2 Characteristic lines
6.2.1 Sensor characteristic lines
 6‒1 Temperature sensor
Measured temperature in °C
-20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120
Sensor resistance in kOhm according to standard or manufacturer's indications
t
DHW1
, t
V,BH
NTC 98.66 56.25 33.21 20.24 12.71 8.20 5.42 3.66 2.53 1.78 1.28 0.93 0.69 0.52 0.36
t
R
, t
V
, t
DHW2
, t
DC
NTC - - 65.61 39.9 25 16.09 10.62 7.176 4.96 3.497 2.512 1.838 1.369 - -