8 From " 6‒3 Maximum refrigerant filling permitted in a
room"[435]: A
room
=15m² →m
max
=1.32kg
9 dm=1.9kg–1.32kg=0.58kg
10 From " 6‒5 Minimum area of the ventilation opening"[435]:
dm=0.58kg →VA
min
=294cm²