Drive type A B C D
0075 2-0114 2
0072 5-0105 5
0041 6-0052 6
80
(3.15)
80
(3.15)
300
(11.81)
100
(3.94)
0140 2-0205 2
0140 5-0205 5
0062 6-0100 6
80
(3.15)
()
80
(3.15)
300
(11.81)
300
(11.81)
0261 2-0300 2
0261 5-0300 5
0125 6-0208 6
50
(1.97)
80
(3.15)
400
(15.75)
250 / 350
(9.84) / (13.78)
()
To change the fan with the motor cables connected, the necessary clearance on the 2 sides of the drive is 150 mm (5.91 inch).
The minimum clearance to change the fan.
Table 7: Necessary Quantity of Cooling Air
Drive type
The quantity of cooling air [m
3
/h]
The quantity of cooling air [CFM]
0003 2-0012 2
0003 5-0012 5
70 41.2
0017 2-0031 2
0016 5-0031 5
190 112
0048 2-0061 2
0038 5-0061 5
0004 6-0034 6
425 250
0075 2-0114 2
0072 5-0105 5
0041 6-0052 6
425 250
0140 2-0205 2
0140 5-0205 5
0062 6-0100 6
650 383
0261 2-0300 2
0261 5-0300 5
0125 6-0208 6
1000 589
Mounting the Unit
Operating guide | VACON® NXS/NXP Air-cooled
DPD00910G | 35
Danfoss A/S © 2018.06

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Vacon NXP Series and is the answer not in the manual?

Danfoss Vacon NXP Series Specifications

General IconGeneral
BrandDanfoss
ModelVacon NXP Series
CategoryController
LanguageEnglish

Related product manuals