Parameter 9-27 Parameter Edit
Table 550: Parameter 9-27 Parameter Edit
Default value: [1] Enabled
Change during operation: False
Parameters can be edited via:
PROFIBUS
The standard RS485 interface
The LCP
Parameter 9-28 Process Control
Table 551: Parameter 9-28 Process Control
Default value: [1] Enable cyclic master
Change during operation: False
Process control (setting of control word, speed reference, and process data) is possible via either PROFIBUS or standard fieldbus, but
not both simultaneously. Local control is always possible via the LCP. Control via process control is possible via either terminals or
fieldbus depending on the settings in parameter 8-50 Coasting Select to parameter 8-56 Preset Reference Select.
Parameter 9-44 Fault Message Counter
Table 552: Parameter 9-44 Fault Message Counter
9-44 Fault Message Counter
Parameter type: Range, 0 - 65535