Option
Name
Description
[4]
SLS-b
[5]
Disable
[8]
SO mon
[10]
None
[20]
Internal event OK
[30]
No function
Parameter 42-21 Type
Table 1381: Parameter 42-21 Type
42-21 Type
Default Value: [0] NCNC
Parameter Type: Option
Setup: All setups
Conversion Index: -
Data Type: Uint8
Change during operation: False
Option
Name
Description
[0]*
NCNC
[1]
Antivalent
[2]
NC
[3]
NO
Parameter 42-22 Discrepancy Time
Table 1382: Parameter 42-22 Discrepancy Time
42-22 Discrepancy Time
Default Value: 10 ms
Parameter Type: Range, 0 - 5000 ms
Setup: All setups
Conversion Index: -3
Data Type: Uint16
Change during operation: False
An adjustable filter time prevents faults caused by temporary discrepancy.
Parameter 42-23 Stable Signal Time
Table 1383: Parameter 42-23 Stable Signal Time
42-23 Stable Signal Time
Default Value: 10 ms
Parameter Type: Range, 0 - 5000 ms
Setup: All setups
Conversion Index: -3
Data Type: Uint16
Change during operation: False
An adjustable signal filter in the safety option suppresses temporary signal changes using test pulse pattern.
Parameter 42-24 Restart Behaviour
Table 1384: Parameter 42-24 Restart Behaviour
42-24 Restart Behaviour
Default value: [0] Manual
Parameter type: Option
Setup: All setups
Conversion index: -
Data type: Uint8
Change during operation: False
AU275636650261en-000101 / 130R0334 | 671Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide