8 Electrical Installation
8.1 Connections- Frame Sizes A, B and C
NOTE
Cables General
All cabling must comply with national and local
regulations on cable cross-sections and ambient
temperature. Copper (75°C) conductors are recommended.
Aluminium Conductors
Terminals can accept aluminium conductors but the
conductor surface has to be clean and the oxidation must
be removed and sealed by neutral acid-free Vaseline
grease before the conductor is connected.
Furthermore the terminal screw must be retightened after
two days due to softness of the aluminium. It is crucial to
keep the connection a gas tight joint, otherwise the
aluminium surface will oxidize again.
Tightening-up Torque
Frame size 200 - 240 V 380 - 500 V 525 - 690 V Cable for: Tightening up torque
A1 0.25-1.5 kW 0.37-1.5 kW -
Mains, Brake resistor, load sharing, Motor cables
0.5-0.6 Nm
A2 0.25-2.2 kW 0.37-4 kW -
A3 3-3.7 kW 5.5-7.5 kW -
A4 0.25-2-2 kW 0.37-4 kW
A5 3-3.7 kW 5.5-7.5 kW -
B1 5.5-7.5 kW 11-15 kW - Mains, Brake resistor, load sharing, Motor cables 1.8 Nm
Relay 0.5-0.6 Nm
Earth 2-3 Nm
B2 11 kW 18.5-22 kW 11-22 kW Mains, Brake resistor, load sharing cables 4.5 Nm
Motor cables 4.5 Nm
Relay 0.5-0.6 Nm
Earth 2-3 Nm
B3 5.5-7.5 kW 11-15 kW - Mains, Brake resistor, load sharing, Motor cables 1.8 Nm
Relay 0.5-0.6 Nm
Earth 2-3 Nm
B4 11-15 kW 18.5-30 kW - Mains, Brake resistor, load sharing, Motor cables 4.5 Nm
Relay 0.5-0.6 Nm
Earth 2-3 Nm
C1 15-22 kW 30-45 kW - Mains, Brake resistor, load sharing cables 10 Nm
Motor cables 10 Nm
Relay 0.5-0.6 Nm
Earth 2-3 Nm
C2 30-37 kW 55-75 kW 30-75 kW Mains, motor cables
14 Nm (up to 95 mm
2
)
24 Nm (over 95 mm
2
)
Load Sharing, brake cables 14 Nm
Relay 0.5-0.6 Nm
Earth 2-3 Nm
C3 18.5-22 kW 30-37 kW - Mains, Brake resistor, load sharing, Motor cables 10 Nm
Relay 0.5-0.6 Nm
Earth 2-3 Nm
C4 37-45 kW 55-75 kW - Mains, motor cables
14 Nm (up to 95 mm
2
)
24 Nm (over 95 mm
2
)
Load Sharing, brake cables 14 Nm
Relay 0.5-0.6 Nm
Earth 2-3 Nm
Electrical Installation FC 300 Design Guide
MG.33.BD.02 - VLT
®
is a registered Danfoss trademark 157
8 8

Table of Contents

Other manuals for Danfoss VLT AutomationDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive and is the answer not in the manual?

Danfoss VLT AutomationDrive Specifications

General IconGeneral
Supply Voltage3 x 200-240 V ±10% 3 x 380-500 V ±10% 3 x 525-600 V ±10%
EnclosureIP20
Output Power Range0.25 kW - 1.5 MW
Communication ProtocolsModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short circuit, Ground fault, Motor overload
Ambient Temperature Range-10°C to +50°C (14°F to 122°F)