4 FC 300 Selection
4.1 Electrical Data - 200-240V
Mains Supply 3 x 200 - 240V AC
FC 301/FC 302 PK25 PK37 PK55 PK75 P1K1 P1K5 P2K2 P3K0 P3K7
Typical Shaft Output [kW] 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 3.7
Enclosure IP20/IP21 A2 A2 A2 A2 A2 A2 A2 A3 A3
EnclosureIP 20 (FC 301 only) A1 A1 A1 A1 A1 A1 - - -
Enclosure IP55, 66 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A5 A5
Output current
Continuous
(3 x 200-240V ) [A]
1.8 2.4 3.5 4.6 6.6 7.5 10.6 12.5 16.7
Intermittent
(3 x 200-240V ) [A]
2.9 3.8 5.6 7.4 10.6 12.0 17.0 20.0 26.7
Continuous
kVA (208V AC) [kVA]
0.65 0.86 1.26 1.66 2.38 2.70 3.82 4.50 6.00
Max. input current
Continuous
(3 x 200-240V ) [A]
1.6 2.2 3.2 4.1 5.9 6.8 9.5 11.3 15.0
Intermittent
(3 x 200-240V ) [A]
2.6 3.5 5.1 6.6 9.4 10.9 15.2 18.1 24.0
Additional specifications
IP20, 21 max. cable cross section
5)
(mains, motor, brake and load
sharing) [mm
2
(AWG )]
2)
4,4,4 (12,12,12)
(min. 0.2(24))
IP55, 66 max. cable cross section
5)
(mains, motor, brake and load
sharing) [mm
2
(AWG)]
4,4,4 (12,12,12)
Max. cable cross section
5)
with
disconnect
6,4,4 (10,12,12)
Estimated power loss
at rated max. load [W]
4)
21 29 42 54 63 82 116 155 185
Weight, enclosure IP20 [kg] 4.7 4.7 4.8 4.8 4.9 4.9 4.9 6.6 6.6
A1 (IP20) 2.7 2.7 2.7 2.7 2.7 2.7 - - -
A5 (IP55, 66) 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5
Efficiency
4)
0.94 0.94 0.95 0.95 0.96 0.96 0.96 0.96 0.96
0.25 - 3.7kW only available as 160% high overload.
FC 300 Selection FC 300 Design Guide
60 MG.33.BD.02 - VLT
®
is a registered Danfoss trademark
44