4.4 Electrical Data - 525-690V
Mains Supply 3 x 525- 690V AC
FC 302 P11K P15K P18K P22K
High/ Normal Load
1)
HO NO HO NO HO NO HO NO
Typical Shaft output at 550V
[kW]
7.5 11 11 15 15 18.5 18.5 22
Typical Shaft output at 575V
[HP]
11 15 15 20 20 25 25 30
Typical Shaft output at 690V
[kW]
11 15 15 18.5 18.5 22 22 30
Enclosure IP21, 55 B2 B2 B2 B2
Output current
Continuous
(3 x 525-550V) [A]
14 19 19 23 23 28 28 36
Intermittent (60 sec overload)
(3 x 525-550V) [A]
22.4 20.9 30.4 25.3 36.8 30.8 44.8 39.6
Continuous
(3 x 551-690V) [A]
13 18 18 22 22 27 27 34
Intermittent (60 sec overload)
(3 x 551-690V) [A]
20.8 19.8 28.8 24.2 35.2 29.7 43.2 37.4
Continuous KVA
(at 550V) [KVA]
13.3 18.1 18.1 21.9 21.9 26.7 26.7 34.3
Continuous KVA
(at 575V) [KVA]
12.9 17.9 17.9 21.9 21.9 26.9 26.9 33.9
Continuous KVA
(at 690V) [KVA]
15.5 21.5 21.5 26.3 26.3 32.3 32.3 40.6
Max. input current
Continuous
(3 x 525-690V) [A]
15 19.5 19.5 24 24 29 29 36
Intermittent (60 sec overload)
(3 x 525-690V) [A]
23.2 21.5 31.2 26.4 38.4 31.9 46.4 39.6
Additional specifications
Max. cable cross section (mains,
load share and brake) [mm
2
(AWG)]
35,-,- (2,-,-)
Max. cable cross section (motor)
[mm
2
(AWG)]
35, 25, 25 (2, 4, 4)
Max cable size with mains
disconnect [mm
2
(AWG)]
2)
16,10,10 (6,8, 8)
Estimated power loss
at rated max. load [W]
4)
228 285 335 375
Weight,
enclosure IP21, IP55 [kg]
27
Efficiency
4)
0.98 0.98 0.98 0.98