0-12 This Set-up Linked to
Option: Function:
While still in set-up 1,
using parameter 0-50 LCP
Copy, copy set-up 1 to set-
up 2. Then set
parameter 0-12 This Set-up
Linked to to [2] Set-up 2.
This starts the linking
process.
130BP076.10
0-12 This Set-up Linked to
0 RPM
0.00A
1(1)
Set-up Handling
0-1*
[2]
Setup 2
Illustration 3.2 Set-up Handling
After the link is complete,
parameter 0-13 Readout: Linked Set-
ups reads set-ups 1 and 2 to
indicate that all not changeable
during operation parameters are
now the same in set-up 1 and set-
up 2. If there are changes to a not
changeable during operation
parameter in set-up 2, for example
parameter 1-30 Stator Resistance (Rs),
they are also changed automatically
in set-up 1. A switch between set-
up 1 and set-up 2 during operation
is now possible.
[0] * Not linked
[1] Set-up 1
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
0-13 Readout: Linked Set-ups
Array [5]
Range: Function:
0* [0 - 255 ] View a list of all the set-ups linked
by parameter 0-12 This Set-up Linked
to. The parameter has 1 index for
each parameter set-up. The value
for each index shows which set-ups
are linked to that parameter set-up.
0-13 Readout: Linked Set-ups
Array [5]
Range: Function:
Index LCP value
0 {0}
1 {1,2}
2 {1,2}
3 {3}
4 {4}
Table 3.1 Set-up Link Example
0-14 Readout: Prog. Set-ups / Channel
Range: Function:
0* [-2147483648
-
2147483647 ]
View the setting of
parameter 0-11 Programming Set-up
for each of the 4 dierent
communication channels. When the
number is shown in hex, as it is in
the LCP, each number shows 1
channel.
Numbers 1–4 show a set-up
number; F stands for the factory
setting, and A stands for an active
set-up. The channels are, from right
to left: LCP, eldbus, USB, HPFB1.5.
Example: The value AAAAAA21h
means that the eldbus channel
uses set-up 2 in
parameter 0-11 Programming Set-up,
the LCP uses set-up 1, and all other
channels use the active set-up.
3.2.3 0-15 Readout: actual setup
0-15 Readout: actual setup
Range: Function:
0* [0 - 255 ] Makes it possible to read out the
active set-up, also when [9] Multi
set-up is selected in
parameter 0-10 Active Set-up.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
30 Danfoss A/S © 10/2019 All rights reserved. M0010001