EasyManua.ls Logo

Danfoss VLT Micro Drive FC 51 - Programming; Local Control Panel (LCP)

Danfoss VLT Micro Drive FC 51
168 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mode 1
1. Enter the main menu.
2. Go to parameter group 1-** Load and Motor.
3. Press [OK].
4. Set motor parameters using nameplate data for
parameter group 1-2* Motor Data.
5. Go to 1-29 Automatic Motor Tuning (AMT).
6. Press [OK].
7. Select [2] Enable AMT.
8. Press [OK].
9. The test runs automatically and indicates when it
is complete.
Mode 2
1. Enter the main menu.
2. Go to parameter group 1-** Load and Motor.
3. Press [OK].
4. Set motor parameters using nameplate data for
parameter group 1-2* Motor Data.
5. Go to 1-29 Automatic Motor Tuning (AMT).
6. Press [OK].
7. Select [3] Complete AMT with Rotating motor.
8. Press [OK].
9. The test runs automatically and indicates when it
is complete.
NOTICE
In mode 2, the rotor rotates during the AMT progress.
Do not add any load on motor in this AMT progress.
Quick Guide
Quick GuideKurzanleitungGuide rapideGuía rápidaGuia RápidoКраткое
руководство
MG02BB4P Danfoss A/S © 05/2016 All rights reserved. 15